P | Q | N | IP | PXR SERIES

POLYLUX’S P | Q | N | IP | PXR SERIES

Control, manoeuvre and isolation single phase transformers

The P, Q, N, IP and PXR series are single-phase transformers with galvanic isolation that have various input and output voltages, configurable by the user. The equipment of these series is generally used for control and switching, although they are also valid for isolating circuits or low power equipment.

These series are subdivided according to their output voltages:

  • P/Q/N inputs 230/400/460V and outputs PB/QB/NB: 12/24V PC/QC/NC: 24/48V PD/QD/ND: 115/230V
  • IPD 230/400/460V inputs and 115/230V outputs
  • PXR 230/400V inputs with ±15V regulation and 230V output

The P, Q and N series includes a rating range as from 40VA up to 5000VA and due to its design, an IP20 degree of protection is obtained that prevents direct electrical contact and perfectly protects the windings.

The IP series includes a rating range as from 100VA up to 2000VA and its IP54 cover makes these devices an ideal solution for outdoor installations.

On the other hand, the PXR series includes a rating range as from 40VA up to 1600VA and has an IP00 degree of protection.

Some of its utilities:

  • The isolation of circuits, being able to increase or decrease the voltage at the output.
  • To change the neutral regime of the installations, being able to go from a two-phase network to a single-phase network or vice versa (this case implies the generation of the artificial neutral).
  • In installations with a certain level of electrical noise, the use of a transformer helps to improve the quality of the electrical network in its secondary.
  • Installations where safety voltages are required (<50 V).
  • Being able to isolate the most sensitive devices in a control panel.
  • Extract different control voltages in an electrical panel.

P
Single phase dry type control and isolation transformers, finished in anti-flash varnished in IP20 enclosure with protection to prevent direct contact with electrical parts.
Rating
From 40 VA to 5000 VA
Input voltage
From 230/400 V to 230/400/460 V
Output voltage
From 12/24 V to 115/230 V
Protection degree
IP-20
Frequency
50/60 Hz
Cooling
ANAN
Ambient temperature
45 ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,6 kV (1 min, 50 Hz) pri-sec – 3,2 kV (1 min, 50 Hz) pri-earth – 2,5 kV (1 min, 50 Hz) sec-earth
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From Screws and DIN Rail to Screws
Q
Single phase dry type control and isolation transformers, finished in anti-flash varnished in IP20 enclosure, resin filled with protection against direct contact with electrical parts.
Rating
From 40 VA to 2500 VA
Input voltage
From 230/400 V to 230/400/460 V
Output voltage
From 12/24 V to 115/230 V
Protection degree
IP-20
Frequency
50/60 Hz
Cooling
From ANAN to AN
Ambient temperature
45ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,6 kV (1 min, 50 Hz) pri-sec – 3,2 kV (1 min, 50 Hz) pri-earth – 2,5 kV (1 min, 50 Hz) sec-earth
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From Screws and DIN Rail to Screws
N
Single phase dry type, cast resin control and isolation transformers, IP20 with protection to prevent direct contact with electrical parts.
Rating
From 40 VA to 5000 VA
Input voltage
From 230/400 V to 230/400/460 V
Output voltage
From 12/24 V to 115/230 V
Protection degree
IP-20
Frequency
50/60 Hz
Cooling
AN
Ambient temperature
45 ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
From 4,6 kV (1 min, 50 Hz) pri-sec – 3,2 kV (1 min, 50 Hz) pri-earth – 2,5 kV (1 min, 50 Hz) sec-earth to 4,6 kV (1 min, 50 Hz) pri-sec 3,2 kV (1 min, 50 Hz) pri-earth 2,5 kV (1 min, 50 Hz) sec-earth
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From Screws and DIN Rail to Screws
IP
Single phase dry type cast resin control and isolation transformers with IP54 protection for outdoor installation.
Rating
From 100 VA to 2000 VA
Input voltage
From 230/400 V to 230/400/460 V
Output voltage
From 12/24 V to 115/230 V
Protection degree
IP-54
Frequency
50/60 Hz
Ambient temperature
45 ºC
Cooling
AN
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,6 kV (1 min, 50 Hz) pri-sec – 3,2 kV (1 min, 50 Hz) pri-earth – 2,5 kV (1 min, 50 Hz) sec-earth
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
Screws
PXR
Single phase dry type isolation transformers, finished in IP00 anti-flash varnished with protection to prevent direct contact with electrical parts.
Rating
From 40 VA to 1600 VA
Input voltage
From 15/0/15/230/400 V to 15/0/15/230/240 V
Output voltage
230 V
Protection degree
IP-00
Frequency
50/60 Hz
Cooling
AN
Ambient temperature
45ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,6 kV (1 min, 50 Hz) pri-sec – 3,2 kV (1 min, 50 Hz) pri-earth – 2,5 kV (1 min, 50 Hz) sec-earth
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From Screws and DIN Rail to Screws
PXD
Single phase dry type isolation transformers with DIN rail, finished in IP00 anti-flash varnished with protection to prevent direct contact with electrical parts.
Rating
From 63 VA to 250 VA
Input voltage
Unique up to 600V (UL) and 750V (CE)
Output voltage
Unique up to 600V (UL) and 750V (CE)
Protection degree
IP-00
Frequency
50/60 Hz
Cooling
AN
Ambient temperature
45ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Standards
IEC/EN/UNE-EN 61558, CE
UL 5085-1 / UL 5085-2
CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06
Certifications
UL RECOGNIZED – CONSTRUCTION ONLY – Component
FILE: E532753
Mounting
Screws and DIN Rail
PX
Single phase dry type isolation transformers, finished in IP00 anti-flash varnished with protection to prevent direct contact with electrical parts.
Rating
From 100 VA to 250 VA
Input voltage
Unique up to 600V (UL) and 750V (CE)
Output voltage
Unique up to 600V (UL) and 750V (CE)
Protection degree
IP-00
Frequency
50/60 Hz
Cooling
AN
Ambient temperature
45ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180 ºC
Windings
Classe HC – 200 ºC
Standards
IEC/EN/UNE-EN 61558, CE
UL 5085-1 / UL 5085-2
CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06
Certifications
UL RECOGNIZED – CONSTRUCTION ONLY – Component
FILE: E532753
Mounting
Screws

Special Manufacturing

We build transformers and inductive elements tailored to your needs.

Tell us about your needs and our engineers will create a solution adapted to your company.