POLYLUX’S TTK SERIES

Three phase to single phase isolating transformers (input-output)

Three-phase to single-phase isolation transformers (input-output)

This series is made up of isolation transformers with 400V three-phase input and 230V single-phase output and have a rating range as from 10kVA up to 500kVA.

They are used in applications where the single-phase consumption in an installation is very large and it is desired to distribute this load in a three-phase system, to avoid important unbalances.

Some of its utilities:

  • It should be noted that, due to its operation, this type of transformer does not achieve a fully balanced distribution in the primary. The current in the central phase of the primary can be twice the nominal current.
  • The use of this type of transformer is recommended for ratings greater than 5kVA, since it is understood that in most industrial installations, for consumption less than or equal to this rating, it does not entail a considerable consumption load. For ratings less than or equal to 5kVA, we recommend using conventional single-phase transformers of the “PD”, “QD”, “ND” or “TK” series.

Constructive features:

  • All the transformers are dipped in anti-flash varnish and then compacted in the oven. This process increases the insulation grade, reduces noise and provides anti-moisture, waterproofed protection.
  • All the connection terminals are made of copper. For transformers with aluminium coils, internal bimetallic AL-CU connections are made by welding with filling and sealing material to ensure a safe, long-lasting connection.
  • The high-power transformers are manufactured with format cores and low losses properties, thus contributing to improving performance

TTKX
Three-phase to single-phase dry-type isolation transformers finished in anti-flash varnished for maximum protection, insulation, noise and vibration reduction.
Rating
From 1 kVA to 100 kVA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-00
Frequency
50/60 Hz
Connection group
V/ invV
Cooling
AN
Ambient temperature
45 ºC
Temperature rise
From Class F – 155ºC to Class H – 180ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
From IEC/EN/UNE-EN 61558, CE to IEC/EN/UNE-EN 60076, CE
TTKW
Three-phase to single-phase dry-type isolation transformers finished in anti-flash varnished in IP23 metal enclosure with protection to prevent direct contact with electrical parts.
Rating
From 1 kVA to 100 kVA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-23 / IK-08
Frequency
50/60 Hz
Connection group
V/ invV
Cover
Metal enclosure RAL 7035 (cat. C3 ISO 12994-2)
Cooling
ANAN
Ambient temperature
45 ºC
Temperature rise
From Class F – 155ºC to Class H – 180ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
From IEC/EN/UNE-EN 61558, CE to IEC/EN/UNE-EN 60076, CE
TTKZ
Three-phase to single-phase dry-type isolation finished in anti-flash varnished in IP54/65 metal enclosure with protection for outdoor installation.
Rating
From 1 kVA to 100 kVA
Input voltage
400 V
Output voltage
230 V
Protection degree
From IP-65 / IK-10 to IP-54/65 / IK-10
Frequency
50/60 Hz
Connection group
V/ invV
Cover
Metal enclosure RAL 7035 (cat. C4 ISO 12994-2)
Cooling
From ANAN to ANAF
Ambient temperature
45 ºC
Temperature rise
From Class F – 155ºC to Class H – 180ºC
Insulation
From Class F – 155ºC to Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
From IEC/EN/UNE-EN 61558, CE to IEC/EN/UNE-EN 60076, CE
Includes
Silent blocks

Special Manufacturing

We build transformers and inductive elements tailored to your needs.

Tell us about your needs and our engineers will create a solution adapted to your company.