POLYLUX’S TTH SERIES

Three phase transformers for electrical medical installations.

Our TTH series is made up of three-phase isolation transformers with 400V input voltage and 230V output voltage and with rating range as from 1000VA up to 10000VA.

They are designed for use in medical electrical installations, being manufactured in accordance with the IEC/EN 61558-2-15 standard focused on safety in installations in clinical installations, guaranteeing patient safety.

We can find different versions depending on their degree of protection:

  • TTH: IP20 cast resin
  • TTHX: IP00
  • TTHW: Inside IP23 enclosure

TTHX
Three-phase isolation transformers for medical use under IEC/EN 61558-2-15 standard, dry type with anti-flash varnish finished for maximum protection, insulation, noise and vibration reduction.
Rating
From 1000 VA to 10000 VA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-00
Frequency
50/60 Hz
Connection group
YNyn0
Cooling
AN
Ambient temperature
45 ºC
Inrush current
< 8In
Temperature rise
Class F – 155ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,5 kV (1 min, 50 Hz)
No load voltage
< 3 %
Leakage current
0,5 mA (sec-earth)
Standards
IEC/EN/UNE-EN 61558-2-15, CE
Includes
Electrostatic screen between 1º & 2º and bimetal thermal protection
TTHW
Three-phase isolation transformers for medical use under IEC/EN 61558-2-15 standard, dry type finished in anti-flash varnished in IP23 metal enclosure with protection to prevent direct contact with electrical parts.
Rating
From 1000 VA to 10000 VA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-23 / IK-08
Frequency
50/60 Hz
Connection group
YNyn0
Cover
Metal enclosure RAL 7035 (cat. C3 ISO 12994-2)
Cooling
ANAN
Ambient temperature
45 ºC
Inrush current
< 8In
Temperature rise
Class F – 155ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,5 kV (1 min, 50 Hz)
No load voltage
< 3 %
Leakage current
0,5 mA (sec-earth)
Standards
IEC/EN/UNE-EN 61558-2-15, CE
Includes
Electrostatic screen between 1º & 2º and bimetal thermal protection
TTH
Three-phase dry type cast resin isolation transformers for medical use under IEC/EN 61558-2-15 standard for high corrosion and vibration environments.
Rating
From 1000 VA to 10000 VA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-20
Frequency
50/60 Hz
Connection group
YNyn0
Cooling
AN
Ambient temperature
45 ºC
Inrush current
< 8In
Temperature rise
Class F – 155ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
4,5 kV (1 min, 50 Hz)
No load voltage
< 3 %
Leakage current
0,5 mA (sec-earth)
Standards
IEC/EN/UNE-EN 61558-2-15, CE
Includes
Electrostatic screen between 1º & 2º and bimetal thermal protection

Special Manufacturing

We build transformers and inductive elements tailored to your needs.

Tell us about your needs and our engineers will create a solution adapted to your company.