THX
Features
Dry type transformer
Anti-flash varnish finish, offering:
- Protection against corrosive environments
- Increase of electrical isolation
- High compression capacity
- Reduction of noise level
- Increase of product's lifespan
Safety class I
Includes electrostatic screen between primary and secondary terminals and bimetallic temperature sensor
Includes also lifting eyebolts from X VA
Possibility of tailor-made manufacturing
Downloads
THX1000 » | THX2000 » | THX3150 » | THX4000 » | THX5000 » | THX6300 » | THX8000 » | THX10000 » | |
---|---|---|---|---|---|---|---|---|
Rating | 1000 VA | 2000 VA | 3150 VA | 4000 VA | 5000 VA | 6300 VA | 8000 VA | 10000 VA |
Input voltage | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V |
Output voltage | 230 V (115-0-115 V) | 230 V (115-0-115 V) | 230 V (115-0-115 V) | 230 V (115-0-115 V) | 230 V (115-0-115 V) | 230 V (115-0-115 V) | 230 V (115-0-115 V) | 230 V (115-0-115 V) |
Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Protection degree | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 |
Cooling | AN | AN | AN | AN | AN | AN | AN | AN |
Ambient temperature | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC |
Inrush current | < 8In | < 8In | < 8In | < 8In | < 8In | < 8In | < 8In | < 8In |
Temperature rise | Class F – 155ºC | Class F – 155ºC | Class F – 155ºC | Class F – 155ºC | Class F – 155ºC | Class F – 155ºC | Class F – 155ºC | Class F – 155ºC |
Insulation | Class H – 180ºC | Class H – 180ºC | Class H – 180ºC | Class H – 180ºC | Class H – 180ºC | Class H – 180ºC | Class H – 180ºC | Class H – 180ºC |
Windings | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC |
Test voltage | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) | 3,5 kV (1 min, 50 Hz) |
No load voltage | < 3 % | < 3 % | < 3 % | < 3 % | < 3 % | < 3 % | < 3 % | < 3 % |
Leakage current | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) | 0,5 mA (sec-earth) |
Standards | IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
IEC/EN/UNE-EN 61558-2-15, CE UL 5085-1 / UL 5085-2 CAN/CSA C22.2 No 66.1-06, CAN/CSA C22.2 No 66.2-06 |
Certifications | UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532754 |
UL RECOGNIZED – CONSTRUCTION ONLY – Component FILE: E532753 |
Includes | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º | Bimetal thermal contact & electrostatic screen between 1º and 2º |
Weight | 13,9 kg | 26 kg | 27,3 kg | 30,7 kg | 38,5 kg | 39,7 kg | 52,6 kg | 65,9 kg |
Dimensions (AxBxCxDxE) | 160x128x253x100x140 mm 9Ø | 200x164x303x155x154 mm 9Ø | 240x140x355x112x180 mm 9Ø | 240x160x355x122x180 mm 9Ø | 240x170x355x142x180 mm 9Ø | 280x190x405x126x210 mm 9Ø | 280x210x405x146x210 mm 9Ø | 280x220x405x156x210 mm 9Ø |
Quote | ||||||||
Buy |
How to buy?
You can see the prices and buy online if you are registered and located in one of this countries: Austria, Croatia, Czech Republic, Finland, France, Germany, Greece, Hungary, Ireland, Italy, Lithuania, Luxembourg Poland, Slovakia and Sweden
Related series
Special fabrications
We build transformers and inductive elements tailored to your needs.
Explain your needs and our engineers will create a solution adapted to your company.