Single-phase isolation transformers with low inrush (<=5In)
Advantages
Dry type transformer.
Efficiency higher than 95%.
Low losses, reducing the consumption of the installation.
Low noise < 40Db
Low connection peak between 3 and 5In, for B or C curve input protection and at its rated current.
Maximum overload 200% 2 seconds.
Finished in anti-flash varnish, by immersion offering:
- Protection against corrosive environments.
- Increased electrical insulation.
- High compacting power.
- Reduction of the noise level.
- Increased product life.
Safety class I.
IP-65 up to 16 kVA and IP-54 as from 20 kVA (for IP-65 degree consult us), metal enclosure painted with polyester resin RAL 7035 (cat. C4 ISO 12994-2).
Includes cable glands and silent-blocks.
Possibility of customized manufacture if different specifications than standard are suitable.
Applications
- TK5IN transformers are used when galvanic isolation is required in single-phase installations.
- They can be used to switch from Phase-Phase to Phase-Neutral.
- To disconnect the neutral from earth in those installations with grounded Phase-Neutral.
- In installations where we have loads that in normal operation have a high level of earth leakage, the TK5IN transformers can isolate them, thus avoiding the untimely jump of the differential.
- In installations where there may be small voltage peaks or electrical noise, TK5IN transformers help to improve the quality of the signal that feeds the loads.
- In outdoor installations where weather conditions are adverse, the TK5INZ version with IP-54/65 outdoor use offers an optimum solution.
Available accessories
- PT100 sensors.
- Bimetal sensors.
- PTC sensors.
- Temperatura control unit.
- Metal enclosure painted with polyester resin RAL 7035 (cat. C5 ISO 12994-2).
TK5INZ2 » | TK5INZ2.5 » | TK5INZ3.15 » | TK5INZ4 » | TK5INZ5 » | TK5INZ6.3 » | TK5INZ8 » | TK5INZ10 » | TK5INZ12.5 » | TK5INZ16 » | TK5INZ20 » | TK5INZ25 » | TK5INZ31.5 » | TK5INZ40 » | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rating | 2 kVA | 2,5 kVA | 3,15 kVA | 4 kVA | 5 kVA | 6,3 kVA | 8 kVA | 10 kVA | 12,5 kVA | 16 kVA | 20 kVA | 25 kVA | 31,5 kVA | 40 kVA |
Input voltage | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V |
Output voltage | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V |
Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Protection degree | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-65 / IK-10 | IP-54 / IK-10 | IP-54 / IK-10 | IP-54 / IK-10 | IP-54 / IK-10 |
Cooling | ANAN | ANAN | ANAN | ANAN | ANAN | ANAN | ANAN | ANAN | ANAN | ANAN | ANAF | ANAF | ANAF | ANAF |
Ambient temperature | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC |
Temperature rise | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC |
Insulation | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC |
Windings | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC |
Inrush current | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In | < 5In |
Efficiency (%) | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% | >95% |
Noise level (dB) | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB | <40dB |
Test voltage | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) |
Standards | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE |
Includes | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection | Bimetal thermal protection |
Weight | 68 kg | 74 kg | 96 kg | 106 kg | 116 kg | 120 kg | 127 kg | 137 kg | 151 kg | 182 kg | 245 kg | 270 kg | 285 kg | 300 kg |
Dimensions (AxBxCxDxE) | 510x362x689x320x250 mm 11Ø | 510x362x689x320x250 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 694x413x764x370x350 mm 11Ø | 970x625x1150x500x426 mm 12Ø | 970x625x1150x500x426 mm 12Ø | 970x625x1150x500x426 mm 12Ø | 970x625x1150x500x426 mm 12Ø |