TTKX
Features
Dry type transformer
Dipped in anti-flash varnish and then compacted in the oven. This process increases the insulation grade, reduces noise and provides anti-moisture, waterproofed protection.
Inverted V/v connection.
Includes lifting eyebolts
Possibility of tailor-made manufacturing
Applications
- TTK transformers are used for the galvanic isolation of electrical installations for safety reasons.
- TThe TTK series with three-phase input and single-phase output are used to achieve a better balance of the primary currents than by connecting only one phase and one neutral of a three-phase line.
- With the three-phase transformer it is also possible to connect a single load of up to half the mains rating.
- In installations where many single-phase loads have to be connected to the same line, the three-phase transformer can also help to make more rating available on that line.
Available accessories
- Protections in primary and secondary.
- One, two and up to 3 electrostatic screens.
- Class II
- Wheels.
- PT100, PTC or Bimetallic probes.
- Painting C5.
- Different RAL.
- Temperature control unit
- Anti condensation system
- Different IP up to IP-65
CE certificate
TTKX1 » | TTKX1.6 » | TTKX2 » | TTKX2.5 » | TTKX3.15 » | TTKX4 » | TTKX5 » | TTKX6.3 » | TTKX8 » | TTKX10 » | TTKX12.5 » | TTKX16 » | TTKX20 » | TTKX25 » | TTKX31.5 » | TTKX40 » | TTKX50 » | TTKX63 » | TTKX80 » | TTKX100 » | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rating | 1 kVA | 1,6 kVA | 2 kVA | 2,5 kVA | 3,15 kVA | 4 kVA | 5 kVA | 6,3 kVA | 8 kVA | 10 kVA | 12,5 kVA | 16 kVA | 20 kVA | 25 kVA | 31,5 kVA | 40 kVA | 50 kVA | 63 kVA | 80 kVA | 100 kVA |
Input voltage | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V | 400 V |
Output voltage | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V | 230 V |
Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Connection group | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV | V/ invV |
Protection degree | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 | IP-00 |
Cooling | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN | AN |
Ambient temperature | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC | 45 ºC |
Temperature rise | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class F – 155 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC |
Insulation | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC | Class H – 180 ºC |
Windings | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC | Class HC – 200 ºC |
Test voltage | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) | 3 kV (1 min, 50 Hz) |
Standards | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 61558, CE | IEC/EN/UNE-EN 60076, CE | IEC/EN/UNE-EN 60076, CE | IEC/EN/UNE-EN 60076, CE | IEC/EN/UNE-EN 60076, CE | IEC/EN/UNE-EN 60076, CE | IEC/EN/UNE-EN 60076, CE |
Weight | 14,1 kg | 20,4 kg | 23,3 kg | 27,8 kg | 35,2 kg | 40 kg | 48 kg | 58 kg | 72 kg | 88 kg | 112 kg | 139 kg | 164 kg | 191 kg | 234 kg | 277 kg | 340 kg | 394 kg | 436 kg | 507 kg |
Dimensions (AxBxCxDxE) | 240x118x268x100x200mm 9Ø | 240x143x268x125x200mm 9Ø | 300x127x326x102x250mm 9Ø | 300x137x326x112x250mm 9Ø | 300x157x326x132x250mm 9Ø | 300x167x326x132x250mm 9Ø | 360x145x382x122x300mm 11Ø | 360x165x382x142x300mm 11Ø | 420x247x366x142x350mm 11Ø | 420x267x366x162x350mm 11Ø | 480x247x459x136x400mm 11Ø | 480x287x459x166x400mm 11Ø | 480x307x459x186x400mm 11Ø | 640x330x550x159,5x426mm 11Ø | 640x365x550x179,5x426mm 11Ø | 714x400x640x189x426mm 11Ø | 714x425x640x209x426mm 13Ø | 760x550x826x460x470mm 13Ø | 760x550x826x460x470mm 13Ø | 760x550x843x460x470mm 13Ø |
Quote | ||||||||||||||||||||
Buy |
How to buy?
You can see the prices and buy online if you are registered and located in one of this countries: Austria, Croatia, Czech Republic, Finland, France, Germany, Greece, Hungary, Ireland, Italy, Lithuania, Luxembourg Poland, Slovakia and Sweden
Related series
Special fabrications
We build transformers and inductive elements tailored to your needs.
Explain your needs and our engineers will create a solution adapted to your company.