Features

Dry type transformer

Dipped in anti-flash varnish and then compacted in the oven. This process increases the insulation grade, reduces noise and provides anti-moisture, waterproofed protection.

Metalic box IP-65 up to 16 kVA and IP-54 as from 20 kVA (for IP-65 degree consult us) enclosure painted with Polyester resin RAL 7035 (cat. C4 ISO 12994-2).

Inverted V/v connection.

Includes lifting eyebolts.

Possibility of tailor-made manufacturing.

Applications

  • TTK transformers are used for the galvanic isolation of electrical installations for safety reasons.
  • TThe TTK series with three-phase input and single-phase output are used to achieve a better balance of the primary currents than by connecting only one phase and one neutral of a three-phase line.
  • With the three-phase transformer it is also possible to connect a single load of up to half the mains rating.
  • In installations where many single-phase loads have to be connected to the same line, the three-phase transformer can also help to make more rating available on that line.

Available accessories

  • Protections in primary and secondary.
  • One, two and up to 3 electrostatic screens.
  • Class II
  • Wheels.
  • PT100, PTC or Bimetallic probes.
  • Painting C5.
  • Different RAL.
  • Temperature control unit
  • Anti condensation system
  • Different IP up to IP-65

CE certificate

TTKZ1 » TTKZ1.6 » TTKZ2 » TTKZ2.5 » TTKZ3.15 » TTKZ4 » TTKZ5 » TTKZ6.3 » TTKZ8 » TTKZ10 » TTKZ12.5 » TTKZ16 » TTKZ20 » TTKZ25 » TTKZ31.5 » TTKZ40 » TTKZ50 » TTKZ63 » TTKZ80 » TTKZ100 »
Rating 1 kVA 1,6 kVA 2 kVA 2,5 kVA 3,15 kVA 4 kVA 5 kVA 6,3 kVA 8 kVA 10 kVA 12,5 kVA 16 kVA 20 kVA 25 kVA 31,5 kVA 40 kVA 50 kVA 63 kVA 80 kVA 100 kVA
Input voltage 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V 400 V
Output voltage 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V 230 V
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Connection group V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV V/ invV
Protection degree IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10 IP-54/65 / IK-10
Cover Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2) Metal enclosure RAL 7035 (cat. C4 ISO 12994-2)
Cooling ANAN ANAN ANAN ANAN ANAN ANAN ANAN ANAN ANAN ANAN ANAN ANAN ANAF ANAF ANAF ANAF ANAF ANAF ANAF ANAF
Ambient temperature 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC 45 ºC
Temperature rise Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC
Insulation Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class F – 155ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC Class H – 180ºC
Windings Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC Class HC – 200 ºC
Test voltage 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz) 3 kV (1 min, 50 Hz)
Standards IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 61558, CE IEC/EN/UNE-EN 60076, CE IEC/EN/UNE-EN 60076, CE IEC/EN/UNE-EN 60076, CE IEC/EN/UNE-EN 60076, CE IEC/EN/UNE-EN 60076, CE
Includes Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks Silent blocks
Weight 33,4 kg 44,3 kg 48,8 kg 56 kg 61 kg 69 kg 79 kg 112 kg 128 kg 152 kg 179 kg 204 kg 256 kg 299 kg 342 kg 469 kg 523 kg 565 kg 636 kg 657 kg
Dimensions (AxBxCxDxE) 330x284x463x230x200 mm 11Ø 510x362x689x320x250 mm 11Ø 510x362x689x320x250 mm 11Ø 510x362x689x320x250 mm 11Ø 510x362x689x320x250 mm 11Ø 510x362x689x320x250 mm 11Ø 510x362x689x320x250 mm 11Ø 694x413x764x370x350 mm 11Ø 694x413x764x370x350 mm 11Ø 694x413x764x370x350 mm 11Ø 694x413x764x370x350 mm 11Ø 694x413x764x370x350 mm 11Ø 970x625x1150x500x426 mm 12Ø 970x625x1150x500x426 mm 12Ø 970x625x1150x500x426 mm 12Ø 970x625x1150x500x426 mm 12Ø 970x625x1150x500x426 mm 12Ø 970x625x1150x500x426 mm 12Ø 189x175x215x165x100 mm 6 1050x900x1370x714x485 mm 18Ø
Quote / Buy Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote
How to buy?

You can buy online if you are located in one of this countries: Austria, Croatia, Czech Republic, Finland, France, Germany, Greece, Hungary, Ireland, Italy, Lithuania, Luxembourg Poland, Slovakia and Sweden.

Related series

TTKX THREE-PHASE TO SINGLE-PHASE ISOLATION TRANSFORMERS (INPUT-OUTPUT)
TTKX
Rating
From 1 kVA to 100 kVA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-00
TTKW THREE-PHASE TO SINGLE-PHASE ISOLATION TRANSFORMERS (INPUT-OUTPUT)
TTKW
Rating
From 1 kVA to 100 kVA
Input voltage
400 V
Output voltage
230 V
Protection degree
IP-23 / IK-08

Special fabrications

We build transformers and inductive elements tailored to your needs.

Explain your needs and our engineers will create a solution adapted to your company.